Case: T08FR01810
Case Details
Entered Date:
07/08/2008
Applicant:
B'NAI B'RITH PANTANO GARDENS INC
Description:
False alarms reported from this address; check all problems and correct:
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01810
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2008 | INSP - LIFE SAFETY | BCOBB | Approved | Series of false alarms from this address; Notification was given as to the seriousness of false alarms. Citations may be issued if they continue. Management was very cooperative. Found error in programming of alarm system - now sending correct signal as to fire or EMS type alarm; also Central alarm had an outdated RP list to contact prior to contacting 911; This has been updated by management to Central Alarm; No reported false alarms since 6/3/2008. Any further problem may be because of a hard-wire problem requiring the system to be re-wired. However the above work seems to have fixed the problem. Case closed. |