Case: T08FR01807
Case Details
Entered Date:
07/07/2008
Applicant:
MAEYN CORP 52% & MARK NIESEN NO-EXEMPT
Description:
sPRINKLER INSPECTION
Outstanding Inspections
Case Number: T08FR01807
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2008 | INSP - FULL | EDESCHAI | Correction Required | 1) MAINTAIN 18 INCHES BELOW A SPRINKLER DEFLECTOR FOR STORAGE 2) mAINTAIN 36 INCHES FROM ELECTRICAL PANELS FOR COMBUSTABLE STORAGE 4) TEST AND REPAIR EMERGENCY LIGHTING AS NECESSARY |