Case: T08FR01805
Case Details
Entered Date:
07/07/2008
Applicant:
KOLB ROAD BUSINESS PARK 1 LLC
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T08FR01805
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2008 | INSP - FULL | EDESCHAI | Correction Required | 1) SPRINKLERS IN THE REST ROOMS, PAINTED, SHALL BE CHANGED OUT 2) NAIL GUN ROOM - THE SPRINKLER NEEDS TO BE LOWERED SO AS TO OPERATE CORRECTLY 3) REPAIR BOTTOM GUAGE AT THE RISER 4) REPAIR THE HANDLE AT THE MAIN DRAIN 5) rEPLACE THE CEILING TILE IN THE RECORDS STORAGE ROOM, BY THE SPRINKLER |