Full Fire Inspection.

Outstanding Inspections

Case Number: T08FR01795
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
07/03/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2- Storage in buildings. Remove all storage from around the water heater located in the kitchen.
07/03/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Unapproved conditions. The electrical outlet located behind the ice machine shall have an approved cover.
07/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection, testing and maintenance. Properly align the hood extinguishing system nozzles with the cooking equipment.
07/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3- Cleaning. Clean and remove all grease accumulation from the hood system or provide documentation of such work.
07/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.4- Extinguishing system service. Provide documentation of the hood system inspection.
07/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4- Power source. The exit signs in the dinning area and the emergency lighting unit in the northwest corner shall have emergency back-up power.
07/03/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. Properly secure the compressed gas cylinders located in the kitchen with a chain or strap to prevent falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01795
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/21/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.