Case: T08FR01795
Case Details
Entered Date:
07/03/2008
Applicant:
SHETTLESWORTH JACK L
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01795
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2- Storage in buildings. Remove all storage from around the water heater located in the kitchen. |
07/03/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. The electrical outlet located behind the ice machine shall have an approved cover. |
07/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Properly align the hood extinguishing system nozzles with the cooking equipment. |
07/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3- Cleaning. Clean and remove all grease accumulation from the hood system or provide documentation of such work. |
07/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.4- Extinguishing system service. Provide documentation of the hood system inspection. |
07/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4- Power source. The exit signs in the dinning area and the emergency lighting unit in the northwest corner shall have emergency back-up power. |
07/03/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. Properly secure the compressed gas cylinders located in the kitchen with a chain or strap to prevent falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01795
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |