Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01793
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3- Working space and clearance. Storage shall not be located within 36 inches of electrical service equipment located in the kitchen. |
07/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3- Cleaning. Clean and remove all grease accumulation from the hood system. |
07/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4- Power source. All exit signs and emergency lighting units located in the dinning room area shall have emergency back-up power. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01793
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |