Case: T08FR01789
Case Details
Entered Date:
07/02/2008
Applicant:
4545 EAST BROADWAY LLC
Description:
Inspection
Outstanding Inspections
Case Number: T08FR01789
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2008 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Stock in storage room shall be maintained 2 feet below ceiling. |
07/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Blanks shall be installed in place of missing breaker switches in east stockroom panel. |
07/02/2008 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Extinguisher in stockroom shall be inspected annually. |
07/02/2008 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6.2 Records of system inspections shall be kept on the premises. |
07/02/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency illumination lights shall be repaired. |
07/02/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.2 North side exit door shall be unobstructed. |
07/02/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.4 Exit signs shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01789
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2008 | INSP - FULL | TKNAPP | Approved |