Case: T08FR01734
Case Details
Entered Date:
07/01/2008
Applicant:
POLIS FAMILY TRUST
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01734
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.3- Equipment rooms. Remove all combustible material being stored in the electrical service rooms. |
07/01/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 506.2- Key box maintenance. Provide a key for fire department access into the building. |
07/01/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7- Hangers and brackets. Mount the portable fire extinguisher on the hanger provided by the west door in the storage area. |
07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3- Locks and latches. Remove the double keyed lock from the double doors located in the waiting area. |
07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3- Exit sign illumination. All exit signs shall be fully illuminated at all times. |
07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Illumination emergency power. Repair or replace the emergency lighting unit located in the "90's" "L" area. |
07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Illumination emergency power. Repair or replace the emergency lighting unit located in the kitchen above the fryers. |
07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Illumination emergency power. Repair or replace the emergency lighting unit located in the server walk way. |
07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Illumination emergency power. Repair or replace the emergency lighting unit located in the waiting area. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01734
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |