Case: T08FR01732
Case Details
Entered Date:
07/01/2008
Applicant:
WAFFLE HOUSE INC
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01732
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Replace the missing ceiling tile located in the back room. |
| 07/01/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3- Cleaning. Clean and remove all grease accumulation from the hood system. |
| 07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4- Bolt locks. Remove the surface bolt from the office door. |
| 07/01/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4- Bolt locks. Remove the surface bolt from the storage room door. |
| 07/01/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. Secure the compressed gas cylinders located in the kitchen with a chain or strap to prevent them from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01732
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |