Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/01/2008

Applicant:

KECK RAY L & MALONE MARILYN CP/RS

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR01728
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
07/01/2008 VIOL - ADMINISTRATION MWAINWRI Violation 2006 IFC 110.1 REMOVE PORTABLE AWNING LAYING ACROSS THE EXIT PATH OUT BACK ( NORTH SIDE)
07/01/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 REPLACE BROKEN SWITCH PLATE COVER IN FIRST BATHROOM REPLACE BROKEN SWITHCH PLATE COVER IN SECOND BATH
07/01/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.4.1 NEED A POWER STRIP UNDER DESK. REMOVE THE CUB ADAPTER.
07/01/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.5 REMOVE EXTENSION CORD BY FRONT DOOR NEXT TO FAN. REMOVE EXTENSION CORD IN FIRST BATH USED FOR MICROWAVE, TOASTER AND HOT PLATE. REMOVE EXTENSION CORD IN SECOND BATH REMOVE EXTENSION CORD IN HALLWALL IN BACK REMOVE EXTENSION CORD LIGHT OVER BACK DOOR.
07/01/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1003.6 KEEP STORE ISLES OPEN AT LEAST 32 INCHES
07/01/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 INSTALL EXIT SIGN AT BACK DOOR

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01728
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/24/2008 INSP - FULL MWAINWRI Approved