Case: T08FR01715
Case Details
Entered Date:
06/26/2008
Applicant:
SILVERADO PLAZA I LLC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: FIELD
Case Number: T08FR01715
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2008 | INSP - FULL | EDESCHAI | Approved | 1) Water motor gong was not working and shall be repaired 2) There is a missing sprinkler head in the bakery freezer, one shall be installed 3) The loaded heads in the bakery shall be cleaned 4) The damaged sprinkler in the deli cooler shall be changed out |