Case: T08FR01712
Case Details
Entered Date:
06/26/2008
Applicant:
LAKIN LLOYD
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01712
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1- Ceiling clearance. All storage shall be maintained 2 feet or more below the ceiling in nonsprinklered buildings. |
06/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. The exposed wiring located by the pump/blower switches shall have an approved cover or be placed in conduit. |
06/26/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Repair all the noles located in the ceiling. |
06/26/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. The northwest and west egress doors shall have only 1 thumb-turn deadbolt for a locking device. NOTE:The door knob can have a thumb-turn locking device on it as long as the lock opens when the knob is turned. |
06/26/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3- Locks and latches. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED," on the inside of the entrance/exit door. |
06/26/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1014.4.2- Aisle accessways in group M. All aisle access ways located in the building shall have a minimum clear width of 30 inches. |
06/26/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.3- Obstructions. The northwest and west egress doors shall not be obstructed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01712
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |