Case: T08FR01711
Case Details
Entered Date:
06/26/2008
Applicant:
GENERAL DENTISTRY REAL ESTATE LLC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01711
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2008 | INSP - FULL | EDESCHAI | Approved | 901.6 MAINTENANCE OF FIRE PROTECTION SYSTEMS 1) FIRE DEPT. CONNECTION REQUIRES 2 CAPS, AND THE TRASH NEEDS TO BE CLEANED OUT 2) A CHROME VIKING 155 DEGREE PENDANT SPRINKLER NEEDS TO BE PLACED IN THE HEAD BOX 3) dENTAL OFFICE RECORDS ROOM, SHELVING AND RECORDS SHALL BE LOWERED TO NO CLOSER THAN 18 INCHES BELOW A SPRINKLER DEFLECTOR 4) AUTO TITLE LOAN, 2 SPRINKLER HEADS EXCEED THE ALLOWABLE DISTANCE OFF WALLS 5) PAYROLL ADVANCE, OFFICE, A HEAD EXCEEDS THE ALLOWABLE DISTANCE OFF WALLS 6) PAYROLL ADVANCE, LOBBY, ONE SPRINKLER HEAD IS HALF IN A WALL AND ANOTHER IS TO CLOSE TO A WALL, RELOCATE AS NEEDED. |