Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T08FR01709
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/26/2008 INSP - FULL EDESCHAI Approved 901.6 mAINTENANCE OF FIRE PROTECTION SYSTEMS 1) INSPECTORS TEST VALVE SHALL HAVE AN IDENTIFICATION SIGN 2) THE COLUMN BY THE FRONT DESK SHALL HAVE AN ADDITIONAL SPRINKLER ON THE NORTH SIDE 3) STORAGE IN THE RECORDS ROOM SHALL BE MAINTAINED 18 INCHES BELOW A SPRINKLER DEFLECTOR 4) AREA OUT SIDE OF THE RECORDS STORAGE ROOM ( NORTH SIDE OF THE OFFICES) SHALL HAVE AN ADDITIONAL SPRINKLER ADDED