Full Fire Inspection.

Outstanding Inspections

Case Number: T08FR01654
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
06/19/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2- Storage in buildings. Storage of combustibles around the water heater is prohibited and shall be removed.
06/19/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3- Working space and clearance. Remove the storage from obstructing the 36 inch working space of the electrical service panel's located in the kitchen.
06/19/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Service, test and tag the portable fire extinguishers and hood system.
06/19/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Door operations. Remove the double-keyed lock from the 2 egress doors that lead to the patio. NOTE:Replace the double-keyed lock with a thumb-turn lock.
06/19/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair or replace the broken emergency lighting unit located in the men's restroom.
06/19/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. The compressed gas cylinders located in the water heater room shall be secured to the wall or fixed object with a chain or strap.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01654
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/19/2008 VIOL - ADMINISTRATION JBURGE Approved TFC 111.1- Order. Cease and desist the use of the 6 burner range and the griddle due to not having an extinguishing system covering the cooking equipment. The two pices of cooking equipment have been red taged. Red tags were removed on 6/19/08 at 1430 hrs. The system was realigned to the original approved cooking equipment. The system is now approved for proper coverage.
09/19/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.