Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/18/2008

Applicant:

GAUSE FAVOR & CLIDIE M JT/RS

Description:

Full Fire Inspection.

Outstanding Inspections

Case Number: T08FR01638
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
06/18/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2- Storage in buildings. The combustible storage located in the office and storage room shall be orderly.
06/18/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Unapproved conditions. The electrical switch used to controll the swamp cooler shall have an approved cover.
06/18/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection, testing and maintenance. Service, test and tag the portable fire extinguisher, or replace the old extinguisher with a new extinguisher.
06/18/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5- Unlatching. Remove one of the two thumb-turn locks from the south entrance/exit door.
06/18/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2- Reliability. Remove the storage from obstructing the south exit access.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01638
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/15/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.