Case: T08FR01638
Case Details
Entered Date:
06/18/2008
Applicant:
GAUSE FAVOR & CLIDIE M JT/RS
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01638
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2- Storage in buildings. The combustible storage located in the office and storage room shall be orderly. |
06/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. The electrical switch used to controll the swamp cooler shall have an approved cover. |
06/18/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Service, test and tag the portable fire extinguisher, or replace the old extinguisher with a new extinguisher. |
06/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.5- Unlatching. Remove one of the two thumb-turn locks from the south entrance/exit door. |
06/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2- Reliability. Remove the storage from obstructing the south exit access. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01638
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |