Case: T08FR01637
Case Details
Entered Date:
06/18/2008
Applicant:
ESPOSITO KIMBERLY S
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T08FR01637
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 310.3- "NO SMOKING" signs. Post "NO SMOKING" signs in the shop area. |
06/18/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 504.2- Maintenance of exterior doors and openings. Post a sign on the exterior side of the doors in the storage room stating,"THIS DOOR BLOCKED." |
06/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. The electrical box located by the compressor in the shop shall have an approved cover. |
06/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. The electrical outlets located in the office behind the tire clock and by the AC unit shall have an approved cover. |
06/18/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.4.2- Nonrequired fire protection systems. Remove the excess fire extinguisher located in the shop. |
06/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3- Locks and latches. Post a sign on the inside of the entrance/exit door in the office/waiting area stating,"THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." |
06/18/2008 | VIOL - TIRE REBUILDING/STORAGE | JBURGE | Correction Required | TFC 2505.4- Exception #1: For existing storage before August 4, 2004 individual piles not exceeding 5,000 square feet (464.5m²) of continuous area shall be located 10 feet (3048.3 mm) from buildings and lot lines for storage not exceeding 6 feet (1829 mm) in height. #1. Tire storage shall not be located within 10 feet of lot lines and the building. |
06/18/2008 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.3.1.4- Responsibility for cleanup. Cleanup the spilled used oil located by the used oil tank and by the dumpster. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01637
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire code violations have been corrected. |