Case: T08FR01622
Case Details
Entered Date:
06/18/2008
Applicant:
WEST MAIN STREET LLC
Description:
Sprinkler and business inspection
Completed Inspections
Case Status: FIELD
Case Number: T08FR01622
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2008 | INSP - FULL | EDESCHAI | Approved | |
| 06/18/2008 | INSP - FULL | EDESCHAI | Approved | 1) 312.1 Vehicle protection shall be afforded the gas meter at the north side of the office building. See attachment. 2) 2903.3 a miminum of 3 feet clearance shall be maintained between the aautomatic sprinklers and the tops of piles 3) 1028.4 Additional exit signs to be provied to be visable at all times 4) 2905.1 Bale size and separation (see attachment) 5) 2905.2 Special bailing conditions (see attachment) 6) 310.2 Additional "No Smoking" signs shall be conspiciously posted |