Case: T08FR01543
Case Details
Entered Date:
06/16/2008
Applicant:
HOM HOWARD & JANET LIVING TR 53 % &
Description:
Full Fire Inspection ARIZONA SPAY NEUTER CLINC Building Rep: Scott Ruth Phone # 624-5005
Outstanding Inspections
Case Number: T08FR01543
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2008 | INSP - FULL | JLONGO | Correction Required | Full Fire prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
06/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all Portable fire extinguishers according to code |
06/16/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix, repair, and bring the rear egress door exit sign into code compliance ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo |