Case: T08FR01526
Case Details
Entered Date:
06/13/2008
Applicant:
PHOENIX DOBSON LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR01526
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3- Working space and clearance. Remove the storage from obstructing the electrical service equipment located in the electrical room. |
| 06/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4- Multiplug adapters. Remove the cube adapter located in the storage room. NOTE:Add another outlet to power more equipment in the storage room. |
| 06/13/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Repair or replace the fire alarm system. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. Remove the chain and padlock from the gate/exit door, or install an exit door in the fencing that is not openable from the outside of the fencing but is readily openable from the inside without a key or special knowledge. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2- Reliability. Remove all obstructions from blocking the exit door located in the nail room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01526
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |