Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/10/2008

Applicant:

MC NAMARA JOHN B & SALLY A

Description:

Full Fire Inspection.

Outstanding Inspections

Case Number: T08FR01497
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
06/10/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC- Unapproved conditions. Replace the missing electrical outlet cover located on the wall by the restrooms in the storage area.
06/10/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Maintenance. Replace all missing ceiling tiles.
06/10/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC703.1- Maintenance. Repair the damaged ceiling located in the storage room.
06/10/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7- Hangers and brackets. Mount the portable fire extinguisher on it's hanger located outback.
06/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Door operations. Remove the double-keyed lock from the east egress door located in the storage room. NOTE: Replace the double-keyed lock with a thumb-turn lock.
06/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Door operations. Remove the locking bar and hardware from the north egress doors.
06/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3- Locks and latches. Post the woprding," THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED," on the inside of the southeast egress door.
06/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4- Bolt Locks. Remove the two surface bolts from the main entrance/exit door. NOTE: Add a thumb-turn lock to the door for more security.
06/10/2008 VIOL - WELDING & OTHER HOT WRK JBURGE Correction Required TFC 2604.2.6- Fire extinguisher. One portable fire extinguisher with a minimum 2-A; 20-B:C rating shall be readily accessible within 30 feet of the location where hot work is being performed. NOTE: Mount the portable fire extinguisher near the hot work area.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01497
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/24/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violatons were corrected.