Description:

Sprinkler inspection

Completed Inspections

Case Status: FIELD
Case Number: T08FR01465
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/09/2008 COMPL - INITIAL INSPECTION EDESCHAI Approved 1) 901.6 Fire protection systems maintenance a) The fire sprrinkler riser shall have a 5 year internal inspection b) The lower guage on sprinkler riser stayed at the same p. s. i. during the flow test, and shall be repaired c) The office area is required to be afforded sprinkler protection. Submittals and permits are required. Submittals shall be made within 60 days and installation completed within 90 days. for your convience please find a copy of fire sprinkler contractors.