Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/06/2008

Applicant:

WILMOT PLAZA LC

Description:

Sprinkler inspection

Outstanding Inspections

Case Number: T08FR01454
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
06/06/2008 INSP - FULL EDESCHAI Correction Required 1) The fire department connection is missing gaskets 2) Wiring shall be removed from sprrinkler piping 3) Provide the correct wrench for replacing sprinkler heads 4) tWO SPRINKLER HEADS ARE CLOSER TOGEATHER THAN THE ALLOWABLE 6 FEET

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01454
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/21/2009 INSP - REINSPECTION BCOBB Approved Went by- building is vacant but neighboring business on same system is approved; Pursley inspected 6337 E Broadway 6/2/09 All approved, tagged, closed.