Case: T08FR01450
Case Details
Entered Date:
06/05/2008
Applicant:
TUPART II LLC
Description:
Sprinkler system OOS call-out.
Outstanding Inspections
Case Number: T08FR01450
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Replace the broken sprinkler head and return the sprinkler system back into service. |
06/05/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.7- System out of service. One fire watch person shall be provided to walk the building until the sprinkler system is back in service. NOTE:See attached form for fire watch details. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01450
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2008 | INSP - LIFE SAFETY | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected and the sprinkler system is back in service as of 1430 6/5/08. |
06/05/2008 | INSP - LIFE SAFETY | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |