Description:

Full fire inspection.

Outstanding Inspections

Case Number: T08FR01422
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 16
End Date Description Inspector Results Comments
06/03/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1- Storage located in the beer cooler shall be maintained at least 18 inches below the sprinkler head deflectors.
06/03/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4- Remove all storage from obstructing the sprinkler system riser pipe and control valves.
06/03/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Replace the 2 missing electrical outlet covers located on the wall in the bar area by the northeast TV.
06/03/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Replace all missing ceiling tiles located in the kitchen. NOTE: Make sure to provide clearance for the sprinkler head to drop down through the tiles.
06/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- All cooking equipment located under the exhaust hood shall be properly covered by the extinguishing system nozzles. NOTE: Add nozzles where needed and align the nozzles with the cooking equipment.
06/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Service, test and tag the kitchen hood extinguishing system.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located by the salad bar just around the corner.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located by the salad bar.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located by the soda machine.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located in the 100's seating area.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located in the expo area on the north wall.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located in the hall by the restrooms.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located on the south side of the 100's seating area.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting unit located on the wall in the bar area by the northeast TV.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the broken emergency lighting units located in both public restrooms.
06/03/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- The compressed gas cylinders located in the riser room shall be properly secured with a chain or strap to prevent falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01422
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/23/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.