Description:

Full fire Inspection.

Outstanding Inspections

Case Number: T08FR01420
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
06/03/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4- Remove all storage from obstructing the sprinkler system riser pipe and control valves.
06/03/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3- Remove all storage from obstructing the electrical service equipment located by the east stair way.
06/03/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Replace all missing ceiling tiles when work has been completed.
06/03/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6- The portable fire extinguisher located by the dairy cooloer shall not be obstructed or obscured from view.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- The exit sign above the double doors that leads into the produce stock room shall be illuminated at all times.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the brocken emergency lighting unit located in the northeast 2nd floor mechanical room on the west wall by the door.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.3- Remove all storage from obstructing the exit and exit access located in the produce stock room.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8- Remove the door knob from the exit door located in the stock room and remove the locaking hardware.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8- Remove the locking hardware from the exit door located by the bakery freezer door.
06/03/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8- Remove the locking hardware from the exit door located in the new computer room.
06/03/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- The blue compressed gas cylinders located in the second floor mechanical rooms shall be properly secured with a chain or strap.
06/03/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- The compressed gas cylinders located in the kitchen shall be properly secured with a chain or strap.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01420
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/02/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.