Case: T08FR01420
Case Details
Entered Date:
06/03/2008
Applicant:
DILLON REAL ESTATE CO INC
Description:
Full fire Inspection.
Outstanding Inspections
Case Number: T08FR01420
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4- Remove all storage from obstructing the sprinkler system riser pipe and control valves. |
06/03/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3- Remove all storage from obstructing the electrical service equipment located by the east stair way. |
06/03/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Replace all missing ceiling tiles when work has been completed. |
06/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6- The portable fire extinguisher located by the dairy cooloer shall not be obstructed or obscured from view. |
06/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3- The exit sign above the double doors that leads into the produce stock room shall be illuminated at all times. |
06/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair the brocken emergency lighting unit located in the northeast 2nd floor mechanical room on the west wall by the door. |
06/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.3- Remove all storage from obstructing the exit and exit access located in the produce stock room. |
06/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.8- Remove the door knob from the exit door located in the stock room and remove the locaking hardware. |
06/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.8- Remove the locking hardware from the exit door located by the bakery freezer door. |
06/03/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.8- Remove the locking hardware from the exit door located in the new computer room. |
06/03/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- The blue compressed gas cylinders located in the second floor mechanical rooms shall be properly secured with a chain or strap. |
06/03/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- The compressed gas cylinders located in the kitchen shall be properly secured with a chain or strap. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01420
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |