Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

06/03/2008

Applicant:

J M K FAMILY PROPERTIES

Description:

Fire Inspection

Completed Inspections

Case Status: FIELD
Case Number: T08FR01397
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/03/2008 INSP - FULL EDESCHAI Approved 1) Sprinkler protection shall be added to the walkin cooler box 2) Alkl storage shall be maintained 18 inches below a sprinkler deflector 3) Add sprinkler protection to the short hall in the game processing area 4) Change out the painted sprinkler head above the freezer in the game processing area