Case: T08FR01393
Case Details
Entered Date:
06/02/2008
Applicant:
JOSEPH ALLAN B & HARIS JT/RS 33.34% &
Description:
Full Inspection
Outstanding Inspections
Case Number: T08FR01393
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords shall not be used in place of permanent wiring. |
06/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Electrical outlets shall have approved covers. |
06/02/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.4 / 1011 An exit sign shall be installed in the "recital" room in order to equip the room with two marked exit doors. Sign shall be internally or externally illuminated at all times. Locking devices on this door shall be openable from the egress side without the use of a key. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01393
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2008 | INSP - FULL | TKNAPP | Approved |