Case: T08FR01360
Case Details
Entered Date:
05/30/2008
Applicant:
EMG REALTY GROUP LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR01360
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORDS USED TO POWER DISPLAY CASES AND POWER STRIPS IN FRONT OF STORE. |
| 05/30/2008 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 INSTALL FIRE EXTINGUISHER BY JEWELERS TABLE WITH A 2A 20BC RATED EXTINGUISHER. |
| 05/30/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1008.1.8 REOVE THE 3 DBL KEYED LOCKS ON REAR EXIT DOOR AND REPLACE WITH THUMB TURNS |
| 05/30/2008 | VIOL - WELDING & OTHER HOT WRK | MWAINWRI | Violation | 2006 IFC 2604.1.6 INSTALL A NON COMBUSTIBLE FLOORING MATERIAL AROUND JEWELERS TABLE. |
| 05/30/2008 | VIOL - COMPRESSED GASES | MWAINWRI | Violation | 2006 IFC 3004.1 SECURE PROPANE, OXYGEN AND ACETYLENE BOTTLES WITH A CHAIN BY WORK BENCH SECURE OXY AND ACETYLENE BOTTLE WITH CHAIN IN FRONT OF STORE |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01360
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2008 | INSP - FULL | MWAINWRI | Approved |