Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/30/2008

Applicant:

EMG REALTY GROUP LLC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR01360
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/30/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.5 REMOVE EXTENSION CORDS USED TO POWER DISPLAY CASES AND POWER STRIPS IN FRONT OF STORE.
05/30/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 INSTALL FIRE EXTINGUISHER BY JEWELERS TABLE WITH A 2A 20BC RATED EXTINGUISHER.
05/30/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8 REOVE THE 3 DBL KEYED LOCKS ON REAR EXIT DOOR AND REPLACE WITH THUMB TURNS
05/30/2008 VIOL - WELDING & OTHER HOT WRK MWAINWRI Violation 2006 IFC 2604.1.6 INSTALL A NON COMBUSTIBLE FLOORING MATERIAL AROUND JEWELERS TABLE.
05/30/2008 VIOL - COMPRESSED GASES MWAINWRI Violation 2006 IFC 3004.1 SECURE PROPANE, OXYGEN AND ACETYLENE BOTTLES WITH A CHAIN BY WORK BENCH SECURE OXY AND ACETYLENE BOTTLE WITH CHAIN IN FRONT OF STORE

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01360
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/01/2008 INSP - FULL MWAINWRI Approved