Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/14/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Fire Prevention Inspection. Jessica Vega 520-292-7113

Outstanding Inspections

Case Number: T08FR01232
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
05/14/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____Service and tag all portable fire extinguishers.
05/14/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____Service and tag the automatic sprinkler system.
05/14/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. _____Remove the curtain from obstructing the sprinkler head, located on the ceiling west of the register.
05/14/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____Remove the roll-up door from obstructing the exit doors located in the stock room. NOTE: The roll-up door requires special knowledge and effort to operate. (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after ___/___/___ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. Thank you. All noted Tucson Fire Code violations have been corrected: ____/____/____ ______________________ John E. Bieg
05/14/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Repair or replace the broken exit sign located in the stock room.
05/14/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency _____Remove all storage from obstructing the Northwest exit doors.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01232
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/10/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.