Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/14/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Fire Prevention Inspection. Starr Boudreau 520-293-9359

Outstanding Inspections

Case Number: T08FR01230
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/14/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. _____Remove the extension cord used to power the small frige. NOTE: Replace it with a fused power strip. (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after ___/___/___ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ John E. Bieg
05/14/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____Service and tag all portable fire extinguishers.
05/14/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____ The exit sign located above the south exit/entrance doors shall be illuminated.
05/14/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____ The north exit sign located in the back room shall be illuminated.
05/14/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system _____Repair or replace the broken emergency lighting units located in the front office and back room.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01230
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/04/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.