Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/14/2008

Applicant:

PARK MALL LLC

Description:

fire inspection

Outstanding Inspections

Case Number: T08FR01229
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/14/2008 INSP - FULL BMERRITT Correction Required IFC 315.2.3 - Keep combustibles clear of water heater.
05/14/2008 INSP - FULL BMERRITT Correction Required IFC 605.3 - Keep area in front of electrical panel clear.
05/14/2008 INSP - FULL BMERRITT Correction Required IFC 703.1 - Repair ceiling above electrical panel.
08/12/2008 INSP - REINSPECTION DGREENLE Correction Required By order of DSD Electrical Inspector Rick Jirouvek (following his inspection on 8/11/09)... have transformer checked by electrical contractor, engineering firm or manufacturer representative to assure that it is not damaged and is operating properly. Inform TFD Prevention of results. He requires no further action at this time.
08/12/2008 INSP - REINSPECTION DGREENLE Correction Required Fill space around conduit runs above electrical panels with fireresistant material to prevent heat/fire from running up wall into attic space.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01229
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/12/2008 COMPL - REINSPECTION DGREENLE Approved Ceiling tiles are currently installed and in place. Thank you. Retain this fire/heat barrier to attic space at all times. Removing tiles to ventilate transformer is a code violation. Consider monitoring temperature around transformer to identify overheating. If smell (possibly from overheating) returns.... 1) Take measures to assure safety of employees and public 2) Try to isolate source of smell 3) Call 911 or notify TFD Fire Prevention (791-4502) depending on acuity of incident.
08/12/2008 COMPL - REINSPECTION DGREENLE Approved Maintenance - Do not let trash encroach into yellow-taped area around electrical panels. - Keep combustables away from water heater.