Case: T08FR01179
Case Details
Entered Date:
05/09/2008
Applicant:
FIESTA LANES LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR01179
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1- Address numbers. Address numbers shall be in accordance with Pima County address display requirements. NOTE: 15 inch numbers required. |
| 05/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4- Multiplug adapters. Remove the cube adapter located in the managers office on the south wall. |
| 05/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5- Extension cords. Remove the orange extension cord located in the manager's office. NOTE: Replace the extension cord and cube adapter with a fused power strip. |
| 05/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. All open spaces in the electrical panels located in the pin set area shall have an approved cover. |
| 05/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.3.3- Obstructed locations. An automatic sprinkler system head shall be installed inside the beer frige for required coverage. |
| 05/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. Remove the door knob from the southeast door in the nursery. |
| 05/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4- Bolt locks. Remove the surface bolt from the door located in the kitchen. |
| 05/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3- Exit sign illumination. All exit signs shall be fully illuminated. NOTE: Exit sign locations; main entrance, sales counter, northwest exit doors, southwest exit doors, southeast exit door and northeast exit door. |
| 05/09/2008 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.3.1.4- Responsibility for cleanup. Clean and properly dispose of the spilled oil and contaminated soil on the south side of the building by the maintenance room. |
| 05/09/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. Secure the compressed gas cylinder located in the kitchen. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01179
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |