Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/08/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full inspection.

Outstanding Inspections

Case Number: T08FR01168
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
05/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Extension cords. Remove the extension cord used to power the small refrigeator. NOTE: Replace the extension cord with a fused power strip or multiplug adapter.
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4- Power source. Repair the two emergency lighting units located in the tanning rooms corridor.
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4- Power source. The exit sign located above the front door shall have emergency back-up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01168
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/22/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.