Case: T08FR01168
Case Details
Entered Date:
05/08/2008
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full inspection.
Outstanding Inspections
Case Number: T08FR01168
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5- Extension cords. Remove the extension cord used to power the small refrigeator. NOTE: Replace the extension cord with a fused power strip or multiplug adapter. |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4- Power source. Repair the two emergency lighting units located in the tanning rooms corridor. |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4- Power source. The exit sign located above the front door shall have emergency back-up power. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01168
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |