Case: T08FR01166
Case Details
Entered Date:
05/08/2008
Applicant:
2004 WAKIMOTO FAMILY LTD PRTNRSHP (THE)
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR01166
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1- Identification. Post a permanent, durable and readily visible sign on the northwest exterior door stating, "SPRINKLER SYSTEM RISER INSIDE." |
| 05/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1- Abatement of electrical hazards. Repair the broken electrical outlet located above the sink by the walk-in frige. |
| 05/08/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Replace all missing or damaged ceiling tiles. Beer room & Banquet room. |
| 05/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Properly align the hood extinguishing system nozzles over the cooking equipment. |
| 05/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Service and tag the kitchen hood extinguishing system. |
| 05/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Service, tag and mount the portable fire extinguisher located in the electrical room. |
| 05/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Service, tag and mount the portable fire extinguisher located in the office. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01166
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |