Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/25/2008

Applicant:

EAST BROADWAY TUCSON CO LLC

Description:

Inspection

Outstanding Inspections

Case Number: T08FR01033
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/25/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Blank for electrical panel
04/25/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 903.3.3 Sprinkler coverage shall be provided for tool room in stockroom.
04/25/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1014.4.1 Aisles in stockroom
04/25/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 605.1 Conduit at OSY valve
04/25/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 605.3 Working space in front of electrical panels.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01033
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/21/2008 INSP - FULL TKNAPP Approved