Case: T08FR01029
Case Details
Entered Date:
04/24/2008
Applicant:
HEIGHTS PROPERTIES LLP
Description:
Full Inspection
Outstanding Inspections
Case Number: T08FR01029
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 Fire extinguishing systems for commercial cooking systems shall be serviced at least every six months. |
04/24/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 The manually operated surface bolt lock located on the kitchen east exit door is prohibited and shall be removed. |
04/24/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 The emergency light fixtures located on the ceiling at the east side of the kitchen, and at the north side of the kitchen near the ice machine shall be repaired. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01029
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2008 | INSP - FULL | TKNAPP | Approved |