Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/21/2008

Applicant:

ARIZONA INN COMPANY LIMITED PARTNERSHIP

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR01005
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/21/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 IN DRY STORAGE (KITCHEN) REPAIR BROKEN SWITHCH COVER.
04/21/2008 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2006 IFC 703.1 REPAIR HOLE IN CEILING IN LAUNDRY DRYER ROOM
04/21/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG K EXTINGUISHER IN MAIN KITCHEN.
04/21/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG SPRINKLER SYSTEM INSTALLED IN THE 9 ROOMS WHICH WERE UPGRADED.
04/21/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.5 NEED A K CLASS EXTINGUISHER IN KITCHEN. MOUNTED ON A WALL IN ACCESSIBLE AREA. BANQUET KITCHEN AREA
04/21/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1004.1 THERE ARE 5 GATES IN THE POOL AREA FOR EXITING AND ALL 5 GATES HAVE DBL KEYED LOCKS INSTALLED IN EACH. AT LEAST ONE GATE NEEDS TO HAVE A THUMB TURN LOCK INSTALLED ON THE INSIDE GATE FOR EMERG. EXITING DURING AFTER HOURS WHEN THE POOL IS LOCKED DOWN.
04/21/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8 REMOVE DBL KEYED LOCK ON EMPLOYEES EXIT IN KITCHEN. REPLACE WITH A THUMB TURN.
04/21/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.9 REMOVE THUMB TURN ON EXIT DOOR IN SAFARI ROOM REMOVE THUMB TURN ON EXIT DOOR IN CATLIN ROOM WHEN PANIC HARDWARE IS ON A DOOR, NO OTHER LOCK IS ALLOWED TO BE ON THAT DOOR.
04/21/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR EXIT SIGN IN EAST LOBBY ENTRANCE
04/21/2008 VIOL - FLAMMABLE FINISHES MWAINWRI Violation 2006 IFC 1504.3.1 SPRAY ROOM SHALL MEET THE DESIGN AND CONSTRUCTION IN ACCORDANCE WITH SECTIONS 1504.4--1504.8.