Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/15/2008

Applicant:

DND NEFFSON CO

Description:

Full Inspection OLIVE GARDEN Building Rep: Denielle P. Williford Phone # 292-1077

Outstanding Inspections

Case Number: T08FR00991
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/15/2008 INSP - FULL JLONGO Correction Required Full Inspection completed. Please Correct the following Tucson Fire Code Violations.
04/16/2008 VIOL - FIRE SERVICE FEATURES JLONGO Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____ Move all storage and obstructions away from sprinkler riser. 510.1 Identification Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____ Properly lable Riser Room door "RISER ROOM" in clear large lettering to properly identify fire service feature.
04/16/2008 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Electrical blanks shall be placed in all open void spaces
04/16/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Hood system nozzles need to be reset to the proper location and maintained at all times. _____ Clean the large amount of dust build up on all sprinkler heads
04/16/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Have main entrance exit sign and Kitchen exit sign serviced in order to maintain back-up power. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo