Case: T08FR00937
Case Details
Entered Date:
04/14/2008
Applicant:
DND NEFFSON CO
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00937
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 15
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Replace the missing hood system filter, located in the main kitchen. |
| 04/14/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6.1- Service and test the fire alarm system or provide documentation of such work within the last year. |
| 04/14/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3- Clean and remove all grease accumulation from the kitchen hood systems, or provide documentation of such work within the last 3 months. |
| 04/14/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.1- Properly align the hood extinguishing system nozzles over the 8 burner range by the muffin cooking area. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 027.5- Repair or replace the emergency lighting unit located on the wall by the door that leads to the restrooms, in the dinning area. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. Remove the surface bolt from the second exit door that leads out of the kitchen. NOTE: Replace the surface bolt with panic hardware. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit by the "VOV" painting in the South dinning area. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located by the exit door in the kitchen. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located in the lobby above the wine display. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located in the mens restroom. NOTE: I was unable to check the lighting unit in the womens restroom at the time of my inspection. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located in the restroom corridor. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located on the north wall in the muffin cooking area. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located on the wall by the Fire Master extinguishing agent boxes, for the main kitchen. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located on the wall by the main entrance/exit. |
| 04/14/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Repair or replace the emergency lighting unit located on the wall in the south west dinning room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00937
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |