Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/09/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00897
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/09/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove all storage from around the water heater located in the back room.
04/09/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the portable fire extinguisher, located in the back room.
04/09/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 All portable fire extinguishers shall be mounted.
04/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The exit sign located above the entrance door shall be illuminated.
04/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The exit sign located in the back room shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00897
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/28/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.