Case: T08FR00897
Case Details
Entered Date:
04/09/2008
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00897
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Remove all storage from around the water heater located in the back room. |
04/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the portable fire extinguisher, located in the back room. |
04/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 All portable fire extinguishers shall be mounted. |
04/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 The exit sign located above the entrance door shall be illuminated. |
04/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 The exit sign located in the back room shall be illuminated. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00897
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |