Outstanding Inspections

Case Number: T08FR00896
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/09/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Storagew shall be maintained a minimum of 18 inches from sprinkler head deflectors. NOTE:Lower the storage from the top of the displays.
04/09/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Clean and remove all dust accumulation from the sprinkler heads.
04/09/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag all portable fire extinguishers.
04/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1006.3 Repair the emergency lighting unitlocated on the ceiling by the exit door in the stock room.
04/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The exit sign located in the stock room shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00896
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/28/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.