Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/08/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection SPORTS BUZZ HAIRCUTS Property Rep: Lisa Burch Phone # 293-2219 Suite: 155

Outstanding Inspections

Case Number: T08FR00864
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/08/2008 INSP - FULL JLONGO Correction Required Full inspection Completed. Please Correct the Following Tucson Fire Code Violations.
04/08/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. -- ---Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____ Service, tag, and properly hang all Portable Fire Extinguishers
04/08/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ Remove inoperable panic hardware from rear egress door to avoid any confusion. Remove double key lock and/or replace with thumb turn lock 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix or replace emergancy exit sign in the rear of the store 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix emergency lighting unit.
04/08/2008 VIOL - COMPRESSED GASES JLONGO Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure compressed gas cylinder located in the employee break room. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo