Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/08/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00860
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
04/08/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Storage shall be maintained a minimum of 18 inches below sprinkler head deflectors.
04/08/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFc 505.1 Post the tenant space number above the entrance door on the exterior side of the building.
04/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 All open spaces in the electrical panel located ini the back room shall be covered by an electrical breaker cover.
04/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 A working space of not less than 36 inches in depth shall be provided in front of the electrical service equipment, located in the back room.
04/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Remove 1 of the 2 locks from the exit door located in the back room.
04/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4 Repair all broken emergency lighting units located in the sales area, restrooms, fish area, exit corridor, back room and kennel.
04/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Removbe all storage from the west exit corridor.
04/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Remove all storage from obstructing the west exit door.
04/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Remove storage from obstructing the exit door located in the back room.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00860
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/30/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrrected.