Case: T08FR00838
Case Details
Entered Date:
04/02/2008
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00838
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Lower the UPS signs, to provide the required minimum of 18 inches below the sprinkler head deflecters. NOTE: THE SIGNS WERE PLACED AGAINST THE WALL. NO NEED TO LOWER. 4/17/08. |
04/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4 Remove the cube adapter located by the bubble wrap table. |
04/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Remove the extension cord used to power the light, located on the desk in the back room. |
04/02/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag all portable fire extinguishers. |
04/02/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.3.3 An automatic sprinkler head shall be installed to properly cover the mail room. NOTE: NOT REQUIRED. REMOVED TOP OF WALL. 4/17/08 |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00838
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/17/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fie Code violations have been corrected. |