Case: T08FR00830
Case Details
Entered Date:
04/02/2008
Applicant:
CENTRO NP HOLDINGS 1 SPE LLC
Description:
Full Inspection Stien Mart Building Rep: Tina Bommarito Phone # 520-887-1199
Outstanding Inspections
Case Number: T08FR00830
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2008 | INSP - FULL | JLONGO | Correction Required | Full Inspection completed. Please correct the following Tucson Fire code Violations. Also on the day of the re-inspect please provide proper proof that the alarm system has be serviced. |
04/02/2008 | VIOL - PRECAUTION AGAINST FIRE | JLONGO | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ alway maintian proper clearance for sprinkler heads |
04/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ You need to alway maintain proper working clearance for all electrical equipment. keep the electrial box in the rear storage room clear and away from debris |
04/02/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. _____ A exit sign needs to added to the second level of the building to indicate the path of egrees as no immediate exit can be seen from that loctaion. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Always maintain proper clearance for all emergancy exits and path of egress. Remove storage material away from the storage room exit door. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo |