Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR00814
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
03/31/2008 INSP - FULL RSPANGLE Violation 1.) TFC 605.6 ELECTRICAL OUTLET OVER SINK IN KITCHEN AREA NEEDS TO HAVE A COVER PLATE INSTALLEED.
03/31/2008 INSP - FULL RSPANGLE Violation 10.) TFC 605.4 THE MULTI-PLUG ADAPTOR ON THE NORTH WALL BY THE COMPUTER TERMINALS NEEDS TO BE REPLACED WITH A UL LISTED FUSED PLUG ADAPTOR.
03/31/2008 INSP - FULL RSPANGLE Violation 11.) TFC 1028.3 A MEANS OF EGRESS SHALL BE FREE FROM OBSTRUCTIONS. REMOVE THE TABLE THAT IS BLOCKING THE EAST EXIT DOOR IN THE EAST DINING ROOM
03/31/2008 INSP - FULL RSPANGLE Violation 2.) TFC 904.5.1 WET CHEMICAL EXTINGUISHING SYSTEM IS PAST DUE FOR THE REQUIRED 6 MO. INSPECTION. NEEDS TO BE IN ACC. WITH UL 300.
03/31/2008 INSP - FULL RSPANGLE Violation 3.) TFC 703.1.1 CEILING OPENING OVER KITCHEN DOORWAY NEEDS TO BE PROTECTED WITH AN APPROVED MATERIAL TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFT STOPPING.
03/31/2008 INSP - FULL RSPANGLE Violation 4.) TFC 3003.5.3 THE COMPRESSED GAS CYLINDERS IN THE KITCHEN NEED TO BE SECURED TO PREVENT FALLING.
03/31/2008 INSP - FULL RSPANGLE Violation 5.) TFC 906.2 PORTABLE 'K' EXTINGUISHERS IN KITCHEN NEED ANNUAL INSPECTION.
03/31/2008 INSP - FULL RSPANGLE Violation 6.) TFC 703.1.1 MISSING CEILING TILE ABOVE THE WATER HEATER IN THE BACK ROOM NEEDS TO BE REPLACED TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFT STOPPING.
03/31/2008 INSP - FULL RSPANGLE Violation 7.) TFC 901.6.2 FIRE SPRINKLER SYSTEM MUST BE INSPECTED ANNUALLY. RECORDS OF SYSTEM INSPECTIONS MUST BE KEPT ON FILE FOR 3 YEARS. A COPY MUST BE MADE AVAILABLE TO THE FIRE CODE OFFICIAL.
03/31/2008 INSP - FULL RSPANGLE Violation 8.) TFC 1008.1.8.5 THE MANUALLY OPERATED FLUSH BOLT ON THE REAR EXIT DOOR IS NOT PERMITTED TO BE USED IN CONJUNCTION WITH THE PANIC HARDWARE. THE FLUSH BOLT LOCK MUST BE REMOVED.
03/31/2008 INSP - FULL RSPANGLE Violation 9.) TFC 906.2 PORTABLE FIRE EXTINGUISHERS ARE DUE FOR THEIR ANNUAL INSPECTION.