Case: T08FR00814
Case Details
Entered Date:
03/31/2008
Applicant:
INTERNATIONAL RESTAURANTS INC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR00814
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 1.) TFC 605.6 ELECTRICAL OUTLET OVER SINK IN KITCHEN AREA NEEDS TO HAVE A COVER PLATE INSTALLEED. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 10.) TFC 605.4 THE MULTI-PLUG ADAPTOR ON THE NORTH WALL BY THE COMPUTER TERMINALS NEEDS TO BE REPLACED WITH A UL LISTED FUSED PLUG ADAPTOR. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 11.) TFC 1028.3 A MEANS OF EGRESS SHALL BE FREE FROM OBSTRUCTIONS. REMOVE THE TABLE THAT IS BLOCKING THE EAST EXIT DOOR IN THE EAST DINING ROOM |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 2.) TFC 904.5.1 WET CHEMICAL EXTINGUISHING SYSTEM IS PAST DUE FOR THE REQUIRED 6 MO. INSPECTION. NEEDS TO BE IN ACC. WITH UL 300. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 3.) TFC 703.1.1 CEILING OPENING OVER KITCHEN DOORWAY NEEDS TO BE PROTECTED WITH AN APPROVED MATERIAL TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFT STOPPING. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 4.) TFC 3003.5.3 THE COMPRESSED GAS CYLINDERS IN THE KITCHEN NEED TO BE SECURED TO PREVENT FALLING. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 5.) TFC 906.2 PORTABLE 'K' EXTINGUISHERS IN KITCHEN NEED ANNUAL INSPECTION. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 6.) TFC 703.1.1 MISSING CEILING TILE ABOVE THE WATER HEATER IN THE BACK ROOM NEEDS TO BE REPLACED TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFT STOPPING. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 7.) TFC 901.6.2 FIRE SPRINKLER SYSTEM MUST BE INSPECTED ANNUALLY. RECORDS OF SYSTEM INSPECTIONS MUST BE KEPT ON FILE FOR 3 YEARS. A COPY MUST BE MADE AVAILABLE TO THE FIRE CODE OFFICIAL. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 8.) TFC 1008.1.8.5 THE MANUALLY OPERATED FLUSH BOLT ON THE REAR EXIT DOOR IS NOT PERMITTED TO BE USED IN CONJUNCTION WITH THE PANIC HARDWARE. THE FLUSH BOLT LOCK MUST BE REMOVED. |
| 03/31/2008 | INSP - FULL | RSPANGLE | Violation | 9.) TFC 906.2 PORTABLE FIRE EXTINGUISHERS ARE DUE FOR THEIR ANNUAL INSPECTION. |