Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/18/2008

Applicant:

AGRO LAND & CATTLE CO INC

Description:

Full inspection done 3/17/2008; Steven Bart- owner 885-0877; "M" occupancy;

Outstanding Inspections

Case Number: T08FR00763
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
03/18/2008 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code [IFC 2006 with modifications] violations:
03/18/2008 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Extension cords: IFC2006 [TFC with modifications] / 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved power strip.
03/18/2008 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Open wire box: IFC2006 [TFC with modifications] / 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner [outlet cover over counter].
03/18/2008 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Temp light used for permanant purpose; IFC2006 [TFC with modifications] / 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ Remove light from over counter.
03/18/2008 VIOL - FIRE PROTECTION SYSTEMS BCOBB Violation Extinguishers not mounted: IFC2006 [TFC with modifications] / 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. Re-inspection date scheduled on or after April 2, 2008. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00763
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/31/2009 INSP - REINSPECTION BCOBB Approved This business is only open after TFD hours - no visualization was ever established, however the owner was aware of TFD code requirements. Case closed.